- Introduction:
- The autofill system comprises of an Allen
Bradley SLC500 PLC based controller to automatically fill the EEV Dewar
mounted on the ESPADONS
Spectrograph. The controller is mounted on the wall inside
of the slit room. Sensors and other cabling feed into the
spectrograph room to allow control, some feedback, and filling of
EEV.
- Refer to Block
Diagram
- Refer to Schematic
Diagram
- Basic Theory of Operation
- Upon start of a fill cycle, the
controller will wait a few seconds and then sense either Dewar 1 or
Dewar 2 Flow sensor's temperature reading. This temperature
reading is a surface mount RTD taped directly to the output side of the
control solenoid. If there is LN2 flow, the temperature reading
should immediately start to decrease.
- The controller will continue to watch
this flow temperature to insure continued LN2 flow. If this
temperature starts to rise significantly, then the controller
determines the tank is empty and automatically flags this tank as being
empty and switches over to the other tank.
- The LN2 flow will continue until the Exhaust Flow temperature drops
below -195 degrees C. This is an indication that EEV is full and
is purging excess LN2 out of the exhaust port. The LN2 flow
is kept on for a few additional seconds to insure this was not a "burp"
and EEV is indeed full.
- The system has
the following features:
- 2 Storage Dewars - Allows filling of
EEV for up to 9 days. When one of the storage dewars empties, the
controller automatically senses the loss of LN2 flow and will
automatically switch over to the second storage dewar.
- Handset control/status:

- LEDs
ON/OFF Switch - (Illuminate the LED
indicators to give current status)
- New Dewar
Switch - Used to reset the the
status bit after replacing an empty storage dewar with a new one.
- Dewar 1 and
Dewar 2 Empty LEDs
- Vacuum Too
High LED (Vacuum level is too high
to allow a safe filling)
- Pressure
Relief 1 and Pressure Relief 2 LED
(The pressure relief sensor on the vent side of the storage
dewar is too high).
- Mode
Switches (When pressing any of these
switches, the LED indicator will illuminate to indicate a switch press):
- Off/Cancel
- Stop the automatic control
of the autofill system.
- Man Fill
- Manually start a fill
sequence. When EEV is full, stop the LN2 flow and revert back to
the Off/Cancel mode.
- Auto Fill
- Sense when either EEV or
exhaust temp has risen above a predetermined set point. At this
time, the controller automatically commences with a fill cycle.
When EEV is full, stop LN2 flow and stay in Auto Fill mode.
- Sched
Fill - Also can be referred to as
"Interval" or "Cycle" fills. Start filling at certain
predetermined times of day. This time can be automatically
calculated based on # of cycles per 24 hour period or set in
registers. In this mode, the fill cycle will start at a
predetermined time of day. When EEV is full, stop LN2 flow and
stay in Sched Fill mode.
- #
Cycles (Display) - Selects number of
intervals or cycles in a 24 hour period. This can be 1, 2, 3 or 4.
- 1 - Once every 24 hours.
- 2 - Twice in 24 hours.
- 3 - Three times in 24 hours.
- 4 - Four times in 24 hours.
- Operation:
- It is assumed all the necessary
connections are made. If there are any questions, please refer
to Block
Diagram
- The PLC's power (in the slit room) should be
on.
- The dewar (EEV) should be pumped and mounted
on the instrument.
- You should have two (2 ea) liquid nitrogen
storage dewars in place. Procedure
on how to replace storage dewar on system.
- Move the LEDs
ON/OFF switch to the ON position.
- Make sure none of the LED error indicators
are set. If they are, you must first remedy the situation before
you will be allowed to start a fill.
- For EEV's case, you should see "2" in the LED display to the right
of #
Cycles/24 Hours switch. This means the autofill
system will fill EEV two times in 24 hours. Currently (16
February 2006) we are filling at 07:30 and 1630 hours. If there
is any doubt about this, contact Grant.
- When you are satisfied things are connected
and on with two full storage dewars hooked up, you can now press:
- Sched Fill
- This will put the system into Scheduled Fill mode.
- Now press
Man Fill: This will start LN2 flow into EEV. When
EEV becomes full, the controller will stop LN2 flow and revert back to Sched Fill mode.
- ========================
Useful Information =======================
- Autofill Status
- LN2 Tank Replacement
Procedure
- Procedure
on how to replace storage dewar on system.
- Autofill PLC - 83.70 (You may enter
the PLC's IP address into a web browser and monitor the various data
registers).
- PLC Data Register
Definitions:
- Temperatures
(Degrees C):
- F23:0 - Vacuum Value (Torr)
- F23:1 - Max Vacuum Value Threshold. (Used
to determine if filling is OK)
- F23:2 - Max vacuum gauge volts.
(Determine
if vacuum gauge volts is valid)
- Value (volts) = (F23:2*10)/32767
- F23:3 - Min vacuum gauge volts. (Determine
if vacuum gauge volts is valid)
- Value (volts) = (F23:3*10)/32767
- 3 - Schedule (Interval) Fill
- N10:1 - 1 - 4 Intervals per 24 hours
15
|
14
|
13
|
12
|
11
|
10
|
9
|
8
|
7
|
6
|
5
|
4
|
3
|
2
|
1
|
0
|
Pressure
Relief 2
Error
|
Pressure
Relief 1
Error
|
No
LN2 Flow
|
Both
Dewars Empty
|
Dewar
2 Empty
|
Dewar
1 Empty
|
Ambient
Temp
Error
|
Exhaust
Temp
Error
|
Flow
2 Temp
Error
|
Flow
1 Temp Error
|
Amb
RTD Error
|
Exhaust
RTD Error
|
Flow
2 RTD
Error
|
Flow
1 RTD Error
|
Vac
Too High
|
Vac
Gauge Volts Error
|
15
|
14
|
13
|
12
|
11
|
10
|
9
|
8
|
7
|
6
|
5
|
4
|
3
|
2
|
1
|
0
|
Software
Reset
|
No
Vacuum
Gauge Enable
(Set for no Vac Gauge)
|
Auto Time Control
0 - User defined fill times.
(N50:10, N50:21, N50:22, N50:23)
Based on # Cycles
(N10:1)
1 -Equal time intervals.
(6, 8, 12, 24 hours)
Based on # Cycles (N10:1)
|
Auto Fill Mode
0 - Trigger on Exhaust Temp (F20:15)
1 - Trigger on Dewar Temp (F20:16
|
|
|
|
|
|
|
|
|
|
Dewar
2
Valid
|
Dewar
1 Valid
|
Dewar
0 Valid
(No Valid Dewars)
|
- N50:10 holds the integer value for "Hour" of start
time. This
is in 24 hour format.
- N50:11 holds the integer value for "Minute" of start
time.
- N50:12 holds the integer value for "Seconds" of start
time but
I don't actually use this. It's just there.
- N50:13 holds the integer value for Last Fill
"Hours"
- N50:14 holds the integer value for Last Fill "Minutes"
- N50:15 holds the integer value for Last Fill "Seconds"
|